Please use this identifier to cite or link to this item: https://hdl.handle.net/20.500.11851/843
Title: Speed Control of Hydraulic Turbines for Grid Synchronization Using Simple Adaptive Add-Ons
Authors: Gezer, Doğan
Taşcıoğlu, Yiğit
Çelebioğlu, Kutay
Keywords: Governor
Model reference adaptive controlspeed
Hydroelectric power plant
Grid synchronization
Gain scheduling
Publisher: SAGE Publications Ltd
Source: Gezer, D., Taşcıoğlu, Y., & Çelebioğlu, K. (2018). Speed control of hydraulic turbines for grid synchronization using simple adaptive add-ons. Measurement and Control, 51(7-8), 276-284.
Abstract: Background: Parameters of the hydroelectric power plant controllers are typically tuned at the nominal operating conditions such as nominal head and single unit operation. Water level variations in reservoir and/or tailwater, and the presence of other active units sharing the penstock are common disturbances to the nominal assumption. Methods: This article proposes two adaptive add-ons, namely gain scheduling and model reference adaptive control, to the existing speed controllers to improve grid synchronization performance when the site conditions are not nominal. The add-ons were designed and tested on a validated dynamic model of a power plant unit by using a software-in-the-loop simulation setup. An off-season scenario is simulated, in which the original controller of the unit cannot bring the turbine to synchronize with the grid due to low gross head. Then, the add-ons were implemented on-site and experiments were performed under similar conditions. The parameter sets used in gain scheduling for different operation bands are determined off-line with the help of operational experience. The model reference adaptive control add-on requires a reference model and a learning rate. A description of the turbine speed-up profile at nominal operating conditions is sufficient to be used as the reference model. The proposed piecewise linear reference model favors stability over speed in settling to the nominal speed. Results: It is experimentally shown that the proposed add-ons compensate the negative effect of head loss in grid synchronization, and perform similar to the ideal performance at the nominal head. Conclusion: Both add-ons can be implemented on the available off-the-shelf speed governor controllers. They are suitable for use in all hydroelectric power plants, especially in unmanned ones, for automatic synchronization with less waste water. © The Author(s) 2018.
URI: https://doi.org/10.1177%2F0020294018786743
https://hdl.handle.net/20.500.11851/843
Appears in Collections:Makine Mühendisliği Bölümü / Department of Mechanical Engineering
Scopus İndeksli Yayınlar Koleksiyonu / Scopus Indexed Publications Collection
WoS İndeksli Yayınlar Koleksiyonu / WoS Indexed Publications Collection

Files in This Item:
File Description SizeFormat 
0020294018786743.pdfPublisher's version699.46 kBAdobe PDFThumbnail
View/Open
Show full item record



CORE Recommender

SCOPUSTM   
Citations

1
checked on Dec 21, 2024

WEB OF SCIENCETM
Citations

2
checked on Dec 21, 2024

Page view(s)

126
checked on Dec 16, 2024

Download(s)

130
checked on Dec 16, 2024

Google ScholarTM

Check




Altmetric


Items in GCRIS Repository are protected by copyright, with all rights reserved, unless otherwise indicated.